
Choose
Model
30SS Variable Speed
- 30SS No Variable
Speed
40SS
Variable Speed - 40SS
No Variable Speed
PRODUCT INFORMATIONAL BULLETIN
INSTALLATION
INSTRUCTIONS Model 30SS
NO-TANK with Constant Pressure Pump (Variable Speed)
Inspect NO-TANK for damage and proper tank pressure. At time
of shipment tank was pre-charged to 20 lbs.
|
 |
Following
are a few simple suggested steps
1. Determine operating pressure of water system and adjust
air pressure in NO-TANK to pump manufactures recommended
pre charge
2. Pump is set in the well and wired to manufactures recommendation
3. Install NO-TANK in the drop pipe string. If a pitless
adaptor is being used, NO-TANK can be located just below
it with an offset nipple, (part # 2002) if you place it
5’ to 10’ below the pitless adaptor, the tank
will be centered and the offset nipple is not needed.
4. Lower the drop pipe into the well so that the NO-TANK
is positioned properly, and continue with the normal installation
at the well.
5. Install the pressure transducer in the home in accordance
with pump manufacturers instructions. If there is reference
to the transducer being within 6’ of pressure tank,
disregard. Since NO-TANK is directly in line there is
no danger of water hammer
6. Complete piping in accordance with all plumbing and
electrical codes.
7. Start system as normal.
8. At start up, pump may not function properly until all
air is removed from system. Cycle pump several times before
any adjustments are made. Once pump is running normally
adjust according to manufactures recommendation.
9. Attach information tag supplied to main shut off valve
or electrical wire in well.
|
Before you leave the site remember you have just installed
NO-TANK one of the most advanced water
systems designed to meet the customers needs.
|
|
Choose
Model
30SS Variable Speed
- 30SS No Variable
Speed
40SS
Variable Speed - 40SS
No Variable Speed
INSTALLATION
INSTRUCTIONS Mode NT30SS
NO-TANK with a Constant Pressure Valve
Inspect NO-TANK for damage and proper tank pressure.
At time of shipment, tank was pre-charged to 20 psi. (Due
to possibility of tank being stored at temperatures above
100 degrees requires tank to be shipped at low per charge)
|
 |
Following are a few simple suggested steps
1.
Determine the operating pressure for the water system
and adjust the air pressure in NO-TANK. For a 50 PSI
valve the tank pre charge should be 40 psi for, 60 psi
valve the pre charge should be 50 psi.
2. Pump is set in the well and wired to pump manufactures
recommendation
3. NO-TANK and constant pressure valve can be located
just below the pitless adaptor if an offset nipple (part
# 2002) is used. If you place tank and valve 5”
to 10’ below the pitless, the tank and valve will
be centered in the well casing and no offset nipple
is required. We do not recommend setting the top of
the pressure tank lower than 10’ since this will
result in the constant pressure valve to be below 20’
in the well and may cause low water pressure in the
home.
4. To install constant pressure valve, the retaining
coupling should be disassembled and installed over the
constant pressure valve. (See drawing) Reassemble and
tighten by hand, then finish with a pipe wrench no more
than ¼ turn. This coupling reinforces the constant
pressure valve and is not meant to provide a watertight
seal. The valve with coupling will hold up to 1000 lbs.
5. Install the constant pressure valve in drop pipe
string.
6. Install a pipe nipple between constant pressure valve
and No-Tank.
7. Install NO-TANK
8. Install short final section of pipe above NO-TANK
and lower pipe into the well so that the NO-TANK is
positioned properly, continue with the normal installation
at the well.
9. Install the pressure switch and other fittings as
required. Adjust the differential setting of the switch
to 26 PSI. (If the switch is a SQ D, tighten the short
spring three turns. This should increase the differential
about 6 pounds.)
10. Start system; allow system to run a few minutes
to remove trapped air from water lines.
11. If pump short cycles, increase pressure switch setting
slightly until short cycling stops. (This may be a 2
to 5# increase in pressure before the problem is corrected)
There is no need to add additional air to NO-TANK
12. Attach Information tag (supplied) to main shut off
valve |
You have just installed NO -TANK, one of the most advanced
water systems designed to meet the needs of the customer.
.
|
|
Choose
Model
30SS Variable Speed
- 30SS No Variable
Speed
40SS
Variable Speed - 40SS
No Variable Speed
INSTALLATION
INSTRUCTIONS for Model 40SS
NO-TANK with Constant Pressure Pump (Variable Speed)
Inspect
NO-TANK for damage and proper tank pressure. At time of shipment
tank was pre-charged to 48 lbs.
|
 |
Following are a few simple suggested steps
1. Determine operating pressure of water system and adjust
air pressure in NO-TANK to pump manufactures recommended
pre charge.
2. Pump is set in the well and wired manufactures recommendation.
3. NO-TANK can be located just below the pitless adaptor
if an offset nipple (part # 2002) is used. If you place
tank 10’ to 20’ below the pitless adaptor
the tank will center itself and no offset nipple is rerquired.
If No-TANK is used with a well seal then it can be positioned
just below the well seal.
4. Lower the drop pipe into the well so that the NO-TANK
is positioned properly, and continue with the normal installation
at the well.
5. Install the pressure transducer in the home in accordance
with pump manufacturers instructions. If there is reference
to the transducer being with- in 6’ of pressure
tank, disregard. Since NO-TANK is directly in line there
is no danger of water hammer
6. Complete piping in accordance with all plumbing and
electrical codes.
7. Start system as normal.
8. At start up, pump may not function properly until all
air is removed from system. Cycle pump several times before
any adjustments are made. Once pump is running normally
adjust to desired pressure.
9. Attach information tag supplied to main shut off valve
or electrical wire in well. |
Before you leave the site remember you have just installed
NO-TANK one of the most advanced water systems designed
to meet the customers needs.
|
|
Choose
Model
30SS Variable Speed
- 30SS No Variable
Speed
40SS
Variable Speed - 40SS
No Variable Speed
INSTALLATION
INSTRUCTIONS for MODEL 40SS
NO-TANK with a Constant Pressure Valve
Inspect
NO-TANK for damage and proper tank pressure. At time of shipment,
tank was pre-charged to 48 psi. |
 |
Following are a few simple suggested steps
1.
Determine the operating pressure for the water system
and adjust the air pressure in NO-TANK. For a 50 PSI
valve the tank pre charge should be 38 psi for 60 psi
valve the pre charge should be 48 psi
2. Pump is set in the well and wired per normal installation
procedures.
3. NO-TANK and constant pressure valve can be located
just below the pitless adaptor if an offset nipple (part
# 2002) is used. If you place tank and valve 10’
to 20’ below the pitless, the tank and valve will
be centered in the well casing and no offset nipple
is required.
4. To install constant pressure valve, the retaining
coupling should be disassembled and installed over the
constant pressure valve. (see drawing) Reassemble and
tighten by hand, than finish with a pipe wrench no more
than 1/4 turn. This coupling reinforces the constant
pressure valve and is not meant to provide a watertight
seal. The valve with coupling will hold up to 1000 lbs.
5. Install the constant pressure valve in drop pipe
string.
6. Install a pipe nipple between constant pressure valve
and No-Tank.
7. Install NO-TANK
8. Install short final section of pipe above NO-TANK
and lower pipe into the well so that the NO-TANK is
positioned properly, continue with the normal installation
at the well.
9. Install the pressure switch and other fittings as
required. Adjust the differential setting of the switch
to 26 PSI. (If the switch is a SQ D, tighten the short
spring three turns. This should increase the differential
about 6 pounds.)
10. Start system; allow system to run a few minutes
to remove trapped air from water lines.
11. If pump short cycles, increase pressure switch setting
slightly until short cycling stops. (This may be a 2
to 5# increase in pressure before the problem is corrected)
There is no need to add additional air to NO-TANK
12. Attach Information tag (supplied) to main shut off
valve |
You have just installed NO -TANK, one of the most advanced
water systems designed to meet the needs of the customer.
|
PRODUCT
INFORMATIONAL BULLETIN
Number 1 July 18, 2003
Placement of check valve when installing the No-Tank.
• When installing the No-Tank, be sure to place the
check valve below the pressure tank. If the check valve is
installed above the pressure tank, it is possible for the
water pressure to increase in the water lines, as the water
in the hot water heater is heated.
• It has been brought to our attention, if two or more
check valves are installed in the drop pipe, that some pump
installers are installing one of the check valves between
the constant pressure valve and the pressure tank. Their reasoning
is that it reduces the backpressure on the constant pressure
valve when the pump is not running. The placement would be
constant pressure valve, short nipple, check valve, short
nipple, and then the No-Tank.
Cycle Stop Valve release
• Cycle Stop has sent out an informational release,
regarding their CSV1 valve, when it is submerged. They are
recommending that a ¼” diameter hole should be
drilled in the valve, to allow the valve to react to changes
in pressure at a faster rate. IT SHOULD ONLY BE DRILLED THROUGH
THE RED LAYER IN THE VALVE. The red layer is about 3/16”
thick, then a 3/16” space, and than a yellow layer.
When the hole is drilled only through the red layer, no water
will leak from the valve. Instructions attached.
(If you have additional questions please contact Cycle Stop
at 800-652-0207)
|
|